        The reason and check method of inverter low voltage and overload trip

        2023-05-20 12:17:11

        Reasons for inverter low voltage trip


        1. The low voltage of the inverter mainly refers to the low voltage of the intermediate DC circuit. Generally, the reason for the low voltage of the intermediate DC circuit comes from two aspects:


        (1) Low voltage from the power input side


        Under normal circumstances, the power supply voltage is 380V, and the allowable error is -15%~10%. After three-phase bridge full-wave rectification, the intermediate DC voltage value is 513V. In some cases, the power line voltage is small and the voltage fluctuation will not be The low voltage trip of the inverter will only cause the inverter to operate if the effective value of the grid voltage is between 80% and 85% of the rated value and the duration exceeds one cycle. The low voltage on the input side of the power supply is mainly due to the fluctuation of the grid voltage or the switching of the main power line, the power supply sine wave amplitude is affected by the lightning strike, the transformer of the power plant itself is overloaded or the load is unbalanced, etc.


        (2) Low voltage from the load side


        The reasons for this are mainly the start-up and application of large equipment, line overload, or starting large motors. The frequency converter is composed of rectifier and inverter. Through the research of the inverter, the low voltage of the inverter refers to the low voltage of the middle DC loop (that is, the input voltage of the inverter is too low). General frequency converters have protection functions of overvoltage, loss of voltage and instantaneous power failure. The inverter device of the inverter is divided into GTR and IGBT. When the inverter device of the inverter is GTR, once the voltage is lost or the power is cut off, the control circuit will stop outputting the signal to the drive circuit, so that the drive circuit and GTR all stop working, the motor It will be in free braking state. When the inverter device is IGBT, after the voltage loss or power failure, the inverter will be allowed to continue to work for a short time td. If the voltage loss or power failure time is totd, the inverter will protect itself and stop running. Generally, td is between 15 and 25 ms, and the power supply “shaking” time is generally more than a few seconds. The inverter will protect itself and stop running, so that the motor stops. Therefore, to solve the problem of inverter low voltage trip can not start from the inverter's inherent time td and voltage loss time to, but must start from the amplitude of the voltage drop.


        2. Solutions for inverter low voltage trip:


        There are two key points to be solved to solve the problem of inverter low voltage trip:


        (1) It is necessary to select the inverter with IGBT inverter device;


        (2) It is necessary to select the inverter that can still work normally under the condition of large voltage loss.


        The motor can rotate, but the running current exceeds the rated value, which is called overload. The basic reflection of overload is that although the current exceeds the rated value, the magnitude of the excess is not large, and generally a large inrush current is not formed.


        The reason and inspection method of inverter overload trip


        1. The main reason for inverter overload


        (1) Malfunction, the current detection part inside the inverter fails, and the detected current signal is too large, causing a trip.


        (2) The mechanical load is too heavy. The main feature of the heavy load is that the motor heats up and can be found by reading the running current from the display.


        (3) The three-phase voltage is unbalanced, which causes the operating current of a certain phase to be too large, resulting in overload tripping. It is characterized by unbalanced motor heating, which may not be found when the operating current is read from the display (because the display only shows one Phase current).


        2. Check method of whether the inverter is overloaded


        (1) Check whether the three-phase voltage on the motor side is balanced. If the three-phase voltage on the motor side is unbalanced, then check whether the three-phase voltage on the output side of the inverter is balanced. If it is not balanced, the problem is within the inverter.


        If the voltage at the output of the inverter is balanced, the problem lies in the line from the inverter to the motor. Check whether the screws of all terminals are tightened. If there is a contactor or other electrical appliances between the inverter and the motor, It should be checked whether the terminals of the related electrical appliances have been tightened and the contact conditions of the contacts are good.


        If the three-phase voltage on the motor side is balanced, you should understand the operating frequency at the time of tripping: if the operating frequency is low and vector control (or no vector control) is not used, first reduce the U/f ratio, if it can still drive the load , It means that the original preset U/f ratio is too high, the peak value of the excitation current is too large, and the current can be reduced by reducing the U/f ratio;


        If the load can not be moved after the reduction, you should consider increasing the capacity of the inverter; if the inverter has vector control function, the vector control method should be used.


        (2) Check whether the motor heats up. If the temperature rise of the motor is not high, first check whether the electronic thermal protection function of the inverter is preset properly. If the inverter still has a margin, the preheating of the electronic thermal protection function should be relaxed. Set value.


        If the temperature rise of the motor is too high, and the overload is normal overload, it means that the motor is overloaded. At this time, whether the transmission ratio should be properly increased to reduce the load on the motor shaft. If it can be increased, increase the transmission ratio. If the transmission ratio cannot be increased, the capacity of the motor should be increased.


        General purpose frequency converter


        label

        QR code

        The public,

        Mobile station
        The public, Mobile station

        Contact

        未標題-8.png 0755-81719517
        未標題-10.png0755-81719530 未標題-11.pngamb@ambition.com.cn
        未標題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

        Navigation

        Home          About

        Product      Case

        Solution      Service

        Job      News

        Contact          

        Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
        主站蜘蛛池模板: 啦啦啦啦www日本在线观看| 国产精品美女AV免费观看| 国产日韩久久免费影院| 男女做aj视频免费的网站| 亚洲一区二区三区水蜜桃| 欧美国产日韩在线| 国产女高清在线看免费观看| 欧美色资源| 999精品全免费观看视频| 中文字幕久久久久人妻 | 国产农村老熟女国产老熟女| 野花社区www视频日本| 日韩人妻av一区二区三区| 夜夜添狠狠添高潮出水| 人妻丰满熟妇av无码区| 麻豆亚洲自偷拍精品日韩另| 一区二区三区国产不卡| 日韩欧美一卡2卡3卡4卡无卡免费2020 | 色久综合色久综合色久综合| 人妻中文字幕精品一页| 国产人成亚洲第一网站在线播放 | 国产精品一区高清在线观看| 婷婷99视频精品全部在线观看| 国产成+人+综合+欧美亚洲| 体验区试看120秒啪啪免费| 国产成人亚洲综合色婷婷秒播| 国产精品亚洲av三区色| 国产成人久久久精品二区三区| 婷婷综合在线观看丁香| 加勒比亚洲天堂午夜中文| 国产精品一区二区不卡91| 最新亚洲人成网站在线影院| 色综合久久网| 国产99视频精品免费视频6| 国产偷国产偷亚洲清高动态图| 欧洲美女粗暴牲交免费观看| 精品国产VA久久久久久久冰| 亚洲国产欧美在线人成| 国产视频一区二区三区四区视频| 青青在线视频一区二区三区| 91中文字幕一区在线|